INTRINSICALLY SAFE EQUIPMENT- Category- Ex ib
Ex ib equipment shall be incapable of causing ignition in normal operation, with a single fault and with the following safety factors:
- 1.5 in normal operation and with one fault
-
- 1.0 with one fault, if the equipment contains no unprotected switch contacts in parts likely to be exposed to a potentially explosive atmosphere and the fault is self-revealing
EX i typical marking: EEx ia IIC T5