EXTRACTS FROM PETROLEUM ACT, 1934
Earth resistance values:
- 4 ohm for electrical systems
- 10 ohms for non-current carrying metallic parts
- all joints in pipelines, valves, etc. shall be bonded and the earth resistance between each joint shall be 1 ohm
Hazardous Areas as per 4th Schedule:
Tables 1 & 2 (as per Form XIII)
- Inter-Distances between tanks (with Classes A, B, C products)
- Distance between tanks and tankers, offices, motors